Features
- Simple and fast to install and operate with colored touchscreen for easy navigation
- Advanced features such as High Temperature cut-out, Autocycle, Event logs for safe and efficient operation
- Built-in ground fault protection functionality evaluated per UL1053 standard. Easiliy adjustable ground fault alarm and trip settings
- Flexible and intuitive set-up reduces set-up time
- USB port for firmware updates, download monitoring reports and remote battery powered setup
- Built-in Form C Alarm relay with flexible set up for Normally Open/Normally Closed operation
Specifications
Alarm Relay: Single Pole Single Throw Relay, Volt-free: Maximum Switching Capacity:1 A @ 24 VDC, 1 A @ 24 VAC
Ambient Temperature: 32 - 105 °F
Circuit Breaker: 30 A, Maximum
Controller Temperature Setting: 32 - 176 °F
Enclosure Material: Polycarbonate
Ground Fault Alarm: 20 - 200 mA
Mounting: DIN Rail
NEMA Rating: 12
Output Relay: 24 A @ 120/208/240/277 +/-10% VAC: 50/60 Hz
Power Consumption, Standby: 9 W
Sensor Cable Length: 10 ft
Sensor Temperature Range: -40 °F
Sensor Tip Diameter: 0.2 in
Sensor Type: Thermistor 2KΩ @ 77°F (25°C), 2-wire
Supply Voltage: 120 - 277 V
Temperature Alarm: 32 - 190 °F