Power
• LQSE2-2DALUNV-D:
–100 V~ 50/60 Hz 150 mA
–120 V~ 50/60 Hz 120 mA
–220-240 V~ 50/60 Hz 80 mA
–277 V~ 50/60 Hz 70 mA
• Lightning strike protection meets ANSI/IEEE standard
62.31-1980. Can withstand voltage surges of up to
6000 V~ and current surges of up to 3000 A
• DALI® Bus Output: 16 V- 128 mA guaranteed supply
current, 250 mA maximum supply current per bus
Standards
• Lutron Quality Systems registered to ISO 9001:2015
• IEC 60669-2-5
• DALI-2® certified - IEC 62386-101 and IEC62386-103 ed.2
• NOM Certified
• ICES-3(B)/NMB-3(B)
• FCC Part 15
• cULus Listed
• UL® 924
Environment
• Ambient temperature operating range: 0 ºC to 40 ºC
(32 ºF to 104 ºF)
• Relative humidity: less than 90% non-condensing
• For indoor use only
Terminals
• Mains wiring: 1.0 mm2
to 4.0 mm2 (18 AWG to 12 AWG)
• DALI® bus wiring: 0.5 mm2
to 4.0 mm2
(20 AWG to 12 AWG)
• QS link wiring: 0.5 mm2
to 2.5 mm2
(20 AWG to 12 AWG)
• CCI and CCI emergency wiring: 0.5 mm2
to 1.5 mm2
(20 AWG to 16 AWG)
Mounting
• Intended to mount within an IP20 (minimum) rated
consumer panel or breaker panel with integrated DIN
rail and dead cover
• 9 DIN modules (161.7 mm)
• For more information on mounting and installation in
panels with integrated DIN rail see the DIN Rail Best
Practices Application Note (P/N 048466) at
www.lutron.com
DALI® Buses
• The DALI® Power Module has an integrated bus power
supply that provides a guaranteed current of 128 mA
(maximum of 250 mA) to power each bus
• The DALI® Power Module is a DALI® single master
controller and therefore no other controllers or sensors
may exist on the same DALI® bus
• Some DALI® loads may be polarity sensitive; refer to
individual manufacturers’ specifications for proper
connection to the DALI® bus
• Short circuit protection with automatic re-start
(610 ms shutdown delay with a 3 second re-start
followed by 800 ms shutdown delay with 160 ms
retry time)
Troubleshooting and Maintenance
Features
• Maintains redundant memory of control gear
programming for ease of single- and multi-control
gear replacement
• After installation, “TEST” button verifies DALI® wiring
on all fixtures