Power Conditioner & Controller
Maximum Output Current, Total - 15 Amps @ 120 Volts AC
Maximum Output Current, Per Outlet - 15 Amps @ 120 Volts AC (subject to a maximum total output current of 15 Amps for all outlets combined)
Filtration - 40 dB @ 100 kHz, 50 dB @ 300 kHz, with 50 Ohm load
Surge Protection Modes - L-G, L-N, N-G
Surge Protection Shutoff - Shuts off rear outlets if surge protection is compromised
Energy Dissipation - 2000 Joules per Mode
Clamping Voltage - 370 Volts
Clamping Time - 1 ns
Wiring Fault Detection - Shuts off rear outlets if a wiring fault is detected at the input [3]
Voltage Sensing Range - 90.0 to 160.0 Volts rms ±1%, measured at input
Current Sensing Range - 0.4 to 15.0 Amps rms ±1% (resistive), measured per outlet
Ambient Temperature Sensing Range - -13.0° to 221.0° ±4° F (-25.0° to 105.0° ±2° C)
Under Voltage Cutoff - Adjustable 90 to 110 Volts, shuts off rear outlets if input drops below set value
Over Voltage Cutoff - Adjustable 130 to 147 Volts, shuts off rear outlets if input exceeds set value
Over Temperature Cutoff - Adjustable -13.0° to 221.0° F (-25.0° to 105.0° C), shuts off rear outlets if input exceeds set value
Turn-On Delay Adjustment - 0.1 to 10.0 seconds, adjustable per each rear outlet
Power
Line Power - 15 Amps @ 120 Volts AC, 60 Hz
Cresnet Power Usage - 0 Watts
Communications
Ethernet - 10/100 Mbps, auto-switching, auto-negotiating, auto-discovery, full/half duplex, TCP/IP, UDP/IP, CIP, DHCP, SSL, TLS, SNMP, Web Server, SMTP e-mail client, web browser setup and control, Crestron control system integration, Crestron Fusion Cloud monitoring, MyCrestron.com monitoring [2]
Cresnet - Cresnet slave mode
Connectors
120V~ 15A 60Hz - (1) Attached 9.8 ft (3 m) grounded AC power cord with NEMA 5-15P plug; Line power input
OUTLET 1 – 8 - (8) NEMA 5-15R AC power outlets; Individually-switched 120 Volt AC power outlets; Locally switched (via power switch) with adjustable turn-on delay per outlet; Local (via LCD) or remote switchable per outlet
TEMP - (1) 2-pin 3.5 mm detachable terminal block; Connection for external temperature sensor (included)
Y, Z, G - (1) 3-pin 3.5 mm detachable terminal block; Cresnet slave port
LAN - (1) 8-pin RJ45 jack; 10Base-T/100Base-TX Ethernet port
G - (1) 6-32 screw; Chassis ground lug
ALWAYS ON (front) - (1) NEMA 5-15R AC power outlet; Unswitched 120 Volt AC power outlet
Controls & Indicators
PWR - (1) Bi-color green/amber LED, indicates line power is present, illuminates amber when the power switch is off and while booting, illuminates green when the power switch is on and the unit is operating normally, turns amber if the rear outlets have been shut off due to a fault condition
FAULT - (1) Red LED, indicates any of the following fault conditions: surge protection is compromised, line and neutral are reversed, or no ground is detected [3]
PROTECT - (1) Green LED, indicates surge protection is fully functional
SHUTDOWN - (1) Amber LED, indicates power to the rear outlets is shut off due to an over-voltage, under-voltage, over-temperature, line input miswire, missing ground, or compromised surge protection fault condition
HW-R - (1) Recessed pushbutton, initiates a hardware reset of the internal CPU (does not affect outlets)
Display - (1) 2 inch (52 mm) diagonal, 220 x 176 pixels, 16-bit TFT active matrix color LCD, displays configuration and status menus
Nav Pad - (1) 5-way navigation pad for menu navigation and adjustment of settings
HOME - (1) Pushbutton, opens or returns to the home menu
BACK - (1) Pushbutton, steps menu back one level
Power Switch - (1) Rocker switch, "On" position initiates turn-on delay sequence to the rear panel outlets, "Off" position turns all rear outlets off immediately
THERMAL BREAKER (rear) - Disrupts power to all outlets in case of an overload condition, press to reset after overload condition is resolved
LAN (rear) - (2) LEDs, green LED indicates Ethernet link status, amber LED indicates Ethernet activity
Environmental
Temperature - 32° to 113° F (0° to 45° C)
Humidity - 10% to 90% RH (non-condensing)
Construction
Chassis - Steel, black finish
Front Panel - Extruded aluminum, black finish, polycarbonate label overlay
Mounting - 1 RU 19-inch rack-mountable (rack ears included)
Temperature Sensor - Adhesive or magnetic mount, 9.8 ft (3.0 m) attached lead
Dimensions
Height - 1.73 in (44 mm)
Width - 17.32 in (440 mm); 19.00 in (483 mm) with rack ears
Depth - 10.56 in (269 mm)
Weight - 8.2 lb (3.8 kg)
Compliance
UL 1449 Type 3 Listed
1. Crestron control system and custom programming sold separately.
2. Email notification and direct integration with MyCrestron.com, Crestron Fusion, and SNMP will be enabled through a future firmware update. Alternately, these services can be integrated now through a Crestron control system with custom programming.
3. Detects most input line wiring faults. Does not detect neutral/ground reversal. Does not discern between ground connections at the AC power line, chassis, or connected equipment (a ground connection at any point will be detected by the PC-300 as normal). The installer is responsible for proper wiring and grounding of this and all connected equipment according to applicable electrical codes, accepted guidelines, and best practices. Proper wiring and function of the AC power source should be verified prior to connecting the PC-300 or any other equipment. Use of this product does not negate the responsibilities of the installer and end-user to exercise all appropriate and required measures for safe and reliable installation and operation