The Viking Model VK696 Attic Sprinkler is UL Listed for both wet and dry pipe systems for use in combustible and non-combustible sloped attic spaces, and can be installed with steel or CPVC piping. (CPVC is allowed on wet pipe systems only.) When used with Viking's Model V-BB (Back to Back) and V-SD (Single Directional) Attic sprinklers, it is possible to utilize a single line of piping at the attic peak, eliminating the need for branch lines and greatly reducing the number of required sprinklers and associated materials. Installed in the upright position, with the deflector parallel to the roof, the VK696 is used in combination with either the Model BB or Model SD to increase the allowable span from 60 ft up to 80 ft (max.). The Model V696 is a glass bulb design with a temperature rating of 200° F, and is offered in either standard brass or ENT plating for areas subject to corrosion. (Note: The Model VK696 is covered by the following U.S. Patent No.: 8,083,002 owned by Tyco)
Spécification
  • K-Factor: K4.2 (60)

    Manufacturer: Viking

    Page: F_042815

    Part Number: 19538

    VK Number: VK696

    Additional Information: NOTICE: The product details indicated below are for general reference only and may vary based on the specific product approval and/or application. Always verify product details with the technical data sheet and consult with the Authority Having Jurisdiction (AHJ).

    Max Pressure: 175 psi (12 bar)

    Response Type: Fast-Attic

    Occupancy Type: Special

    Thread Size: 1/2" NPT (15 mm BSP)

    Min Spacing: Per Standards / Listings

    Max Spacing: Per Standards / Listings

Spécifications techniques
  • Réference unique.vk696-fast-attic-upright-sprinkler-k42
  • Famille de produitsViking Fire Sprinklers
  • Groupe de produitsViking - Attic Sprinkler / Upright
  • TypeObjet (objet simple)
  • Date de publication2021-01-25
  • Numéro d'édition1
En rapport
  • Conçu enÉtats-Unis
  • Fabriqué enÉtats-Unis
Classification
  • BIMobject CatégorieSécurité Incendie - Système de Sprinklers
  • Code ETIMEC011371
  • Nom ETIMSpray sprinkler
  • Nom UNSPSCFire sprinkler heads
  • Code UNSPSC46191610
  • Code Uniclass 2015Pr_70_55_97_84
  • Description de l'Uniclass 2015Sprinkler heads
  • Code CSI MasterFormat 201421 13 00
  • Titre CSI MasterFormat 2014Fire-Suppression Sprinkler Systems
  • Numéro OmniClass23-29 33 11 13
  • Titre OmniClassUpright Sprinkler Heads
  • Code CSI UniFormat IID4010
  • Titre CSI UniFormat IISprinklers
Common.Footer.ValueProp.Image.AltText

Application Design pour Revit

Chargez des familles directement dans votre modèle Revit en un seul clic

Bénéficiez d'un endroit pour accéder plus facilement à de nouveaux objets, stocker vos familles Revit et collaborer avec votre équipe.

  • CocheTravaillez directement avec des objets BIM à côté de Revit
  • Coche 2 Go de stockage dans le cloud : stockez votre contenu Revit
  • Coche Obtenez une analyse du cycle de vie du carbone incorporé (A1-A3) directement depuis Revit