Pubblica i tuoi prodotti
SHARK Field-Adjustable Linear Washdown Lighting

SHARK Field-Adjustable Linear Washdown Lighting

KEY FEATURES

  • Available models with selectable wattages:
    • 2 Ft: 25/20/15W, factory default 25W
    • 4 Ft: 50/40/30W, factory default 50W
    • 8 Ft: 100/80/60W, factory default 100W
  • Field-adjustable CCT: 3500/4000/5000K, factory default 4000K
  • Voltage rating 120-277V
  • Impact-resistant polycarbonate housing
  • Available with smart controls. Multi-sensor remote sold seperately
  • Battery backup available
  • Standard surface-mount brackets and V-hooks for chain mounting.
  • Additional mounting accessory kits available
  • UL Listed for wet locations. UL Marine listed models available.
  • All standard modles are NSF certified and IP66 rated. Marine Listed models
  • are not NSF certified
  • 5-year, no-compromise warranty
Voce di capitolato
  • COMPLIANCE

    • UL Listed
    • Suitable for wet locations. UL Marine listed.
    • IESNA LM-79 & LM-80 Testing
    • DLC Listed: On the Design Lights Consortium (DLC) Qualified Products List, eligible for rebates from DLC Member Utilities, designed to meet DLC 5.1 requirements.
    • IP Ratings: Ingress Protection rating of IP66 for dust and water.
    • NSF: NSF certified by public health and safety.

    FIELD-ADJUSTABLE STRIP LIGHT KEY FEATURES

    • Available models with selectable wattages: 2 Ft: 25/20/15W, factory default 25W; 4 Ft: 50/40/30W, factory default 50W; 8 Ft: 100/80/60W, factory default 100W.
    • Field-adjustable CCT: 3500/4000/5000K, factory default 4000K.
    • Voltage rating 120-277V.
    • Impact-resistant polycarbonate housing.
    • Available with smart controls. Multi-sensor remote sold separately.
    • Battery backup available.
    • Standard surface-mount brackets and V-hooks for chain mounting.
    • Additional mounting accessory kits available.

    CONSTRUCTION

    • Cold Weather Starting: The minimum starting temperature is -40°C (-40°F).
    • Cold Weather Starting for battery backup: The minimum starting temperature is 0°C (32°F).
    • Maximum Ambient Temperature: Suitable for use in up to 40°C (104°F).
    • Maximum Ambient Temperature for battery backup: Suitable for use in up to 40°C (102°F).
    • Mounting: Stainless steel, surface-mount brackets and v-hooks are supplied. Accessory kits available for angled surface, junction box, or tamperproof mounting.
    • Housing: Polycarbonate.
    • Lens: Textured, diffuse polycarbonate lens for low glare and maximum protection.
    • Gasket: Silicone foam.
    • Finish: Formulated for high durability and long-lasting color.
    • Green Technology: Mercury and UV free. RoHs-compliant components.

    LED CHARACTERISTICS

    • LEDs: Long-life, high-efficacy, discrete, surface-mount LEDs.
    • Color Uniformity: RAB's range of Correlated Color Temperature follows the guidelines of the American National Standard for Specifications for the Chromaticity of Solid State Lighting (SSL) Products, ANSI C78.377-2017.

    LIGHTCLOUD

    • Lightcloud Controller Installed:
      • Integrated/embedded networked lighting control.
      • Luminaire-level lighting control.
      • Fixture, Zone, and plug-load control from one powerful device.
      • LLLC - Capable of switching, 0-10V dimming, power/energy monitoring.
      • Can also be used to extend the range of Lightcloud.
      • Mesh network communication protocols.
      • Offers the capability to set the maximum light output to a less-than maximum state of an individual luminaire at the time of installation or commissioning. The High-End Trim functionality is field reconfigurable via the Lightcloud mesh network communication protocols.
      • The Lightcloud Controller can be attached to the fixture, junction box, or electrical panel.
      • DLC system - N1XMLOEATBA.
      • Communication Protocol: Zigbee.
      • Line of Sight: 1,000 feet. Obstructions: 100 feet.
    • Lightcloud Blue Installed:
      • Integrated/embedded networked lighting control.
      • Luminaire-level lighting control.
      • Fixture, Zone, and plug-load control from one powerful device.
      • LLLC - Capable of switching, 0-10V dimming, power/energy monitoring.
      • Can also be used to extend the range of Lightcloud Blue.
      • Utilizes a "BLE Mesh" network communication protocol.
      • Offers the capability to set the maximum light output to a less-than maximum state of an individual luminaire at the time of installation or commissioning. The High-End Trim functionality is field reconfigurable via the Lightcloud "BLE Mesh" network communication protocols.
      • The Lightcloud Blue Controller is designed to be attached to the fixture directly.
      • DLC system - N1XMLOEATBA.
      • Gateway Required: No.
      • Communication Protocol: Bluetooth Mesh.
      • Range: Up to 60 feet between standard building materials. Up to 200 feet clear line of sight.
      • Spacing Criteria: Lightcloud Blue devices should be placed within the specified range to communicate within the Bluetooth Mesh network.

    MICROWAVE OCCUPANCY SENSOR W/DAYLIGHT SENSING, MULTI-FUNCTION SENSOR (OPTIONAL)

    • Operating Voltage: 12V DC.
    • Operating Current: ≤25mA.
    • Detection Area: 25%/50%/75%/100%.
    • Maximum Mounting Height: 20 ft.
    • Customizable Detection Area: 10, 50, 75 or 100%.
    • Hold Time : 5s, 30s, 1min, 3min, 5min, 10min, 20min, 30min.
    • Cut-Off Period: 0s/10s/30s/1min/5min/10min/30min/+ ∞.
    • Cut-Off Dimming level: 10, 20, 30, 50%.
    • Cut-Off Power: ≤0.5W.
    • Daylight Threshold: 2Lux/10Lux/30Lux/50Lux/80Lux/120Lux/Disable.
    • Sensor Principle: High Frequency.
    • Microwave Frequency: 5.8GHz +/- 75MHz.
    • Microwave Power: <0.3mW.
    • Max Detection Range: 46 ft.
    • Operating Temperature: -20°C to +60°C (-4°F to +140°F).
    • Remote Control: Adjust settings using remote control (catalog# MSR1). Only available with 0-10V dimming driver options.

    ELECTRICAL

    • Drivers: Constant Current, Class 2, 120-277V, 50/60 Hz.
    • Dimming Driver: Driver includes dimming control wiring for 0-10V dimming systems. Requires separate 0-10V DC dimming circuit. Dims down to 10%.
    • THD: SHARK2: 3.37% at 120V, 2.15% at 277V; SHARK4: 2.80% at 120V, 3.03% at 277V; SHARK8: 3.26% at 120V, 11.62% at 277V.
    • Power Factor: SHARK2: 95.6% at 120V, 99.8% at 277V; SHARK4: 99.9% at 120V, 97.7% at 277V; SHARK8: 99.9% at 120V, 96.1% at 277V.
    • Surge Protection: 2.5kV.
    • Battery Backup Light Loss Factor: Powers the fixture for a minimum of 90 minutes in the event of a power failure.
      • SHARK2: 0.232.
      • SHARK4: 0.207.
      • SHARK8: 0.104.
    • Note: All values are typical (tolerance +/- 10%).

    PIR SENSOR

    • PIR Sensor Factory Settings:
      • Brightness: 100%.
      • Hold Time: 1 Minute.
      • Daylight: Disabled.
      • Sensitivity: 100%.
      • Stand-By Dimming Level: 20%.
      • Stand-By Time: 1 Minute.
      • Operating Voltage: 12 ± 2V DC.
      • Operating Current: 30mA.
      • Output: DIM 0-10V.
      • Stand-By Power: <0.5W.
      • Brightness: 0%-100%/Quick setting: 70%/80%/90%/100%.
      • Hold Time: 10s/1min/10min/30min.
      • Daylight Threshold: 10Lux/30Lux/50Lux/100Lux/Disable.
      • Lux On-Off: Adopted dual PD technology.
      • Stand-By Time: 1min/30min/60min/+∞.
      • Stand-By Dimming Level: 10%/20%/30%/50%.
      • Detection Angle: ≤120° (wall mounted) 360° (ceiling mounted).
      • Control Line: Black White 12V+ ; Purple: DIM+ ; Pink GND/DIM.
    • Mounting Height: Max 6M (ceiling mounted).
    • Detection Range: Max 8m (ceiling mounted) Max 6m(wall mounted).
    • Operating Temperature: -30°C to 60°C (-22°F to 140°F).

    PERFORMANCE

    • Lifespan: 100,000-hours LED Lifespan based on IES LM-80 results and TM-21 calculations.


Specifiche tecniche
  • Rif. Unicoshark-field-adjustable-linear-washdown-lighting
  • Famiglia di prodottoInterior Lighting
  • Gruppo di famigliaLinear, Surface & Pendant
  • TipoOggetto (oggetto singolo)
  • Data di pubblicazione2024-10-09
  • Numero di versione1
Classificazioni
  • Categoria BIMobjectIlluminazione - Luci lineari
  • Clasificazione IFCApparecchio a luce
  • Codice Uniclass 2015EF_70_80
  • Descrizione Uniclass 2015Lighting
  • Numero OmniClass23-35 47 11
  • Titolo OmniClassLighting Fixtures

Disponibilità Regionale

Nord America
Stati Uniti
Common.Footer.ValueProp.Image.AltText

App di progettazione per Revit

Carica le famiglie direttamente nel tuo modello Revit con un solo clic

Ottieni un posto per accedere più facilmente a nuovi oggetti, archivia le tue famiglie Revit e collabora con il tuo team.

  • Segno di spuntaLavora direttamente con gli oggetti BIM accanto a Revit
  • Segno di spunta 2 GB di spazio di archiviazione cloud: archivia i tuoi contenuti Revit
  • Segno di spunta Ottieni l'LCA (A1-A3) del carbonio incorporato direttamente da Revit