제품 게시
Digital Recirculation Valve, Brain, DRV80R

Digital Recirculation Valve, Brain, DRV80R

DRV80R is a fully digital recirculation valve (DRV) for "point of source" or mechanical room based installation. DRV80 is designed specifically to be the primary water temperature controller in a continuously pumped recirculating hot water system.

Operational Specifications

The enhanced accuracy possible with DRV80 digital technology, combined with its data input/output communication capability equals:
  • Accurate control of blended water drawn from the system at a point of use typically within +/-2°F at draw off points a minimum of 5m downstream of mixing valve during consistent system demand periods
  • Operational water pressure of 10 -150 psig
  • Minimum valve inlet to outlet temperature requirement (system recirculation temperature loss) of 2°F
  • Automatic shutoff of hot water flow upon cold water inlet supply failure
  • Automatic shutoff of hot water flow in the event of a power failure
  • Maintain a consistent system "idling" temperature and control "temperature creep" without the use of a manual throttling device or balance valve.
  • System shall not require a temperature activated pump shut-off device (aquastat).
  • Programmable set point range of 100-160°F (37-71°C) plus full hot/full cold
  • Ability to thermally disinfect at recommended temperatures
  • Programmable 1st level hi/lo temp alarm display
  • Programmable temperature error level for safety shutdown
기술 사양
  • 특징 참조21492
  • 제품군Mixing Valves for Liquid Services
  • 제품분류Hot Water Products - Water Temperature Controls
  • 유형개체 (단일 개체)
  • 게시일2012-12-03
  • 에디션 넘버1
분류
  • BIMobject 카테고리배관 - 밸브

지역 가용성

북미
미국
Common.Footer.ValueProp.Image.AltText

Revit용 Design App

한 번의 클릭으로 Revit 모델에 바로 패밀리를 로드하세요.

새 객체에 더 쉽게 접근하고, Revit 패밀리를 저장하고, 팀과 협업할 수 있는 공간을 확보하세요.

  • 체크 표시Revit 바로 옆에서 BIM 개체로 직접 작업
  • 체크 표시 2GB 클라우드 스토리지 - Revit 콘텐츠 저장
  • 체크 표시 Revit에서 바로 내재 탄소 LCA(A1-A3) 획득