The Excess Pressure Shutdown Valve shall be a diaphragm actuated, pilot controlled valve. The main valve body shall be ductile iron ASTM A 536. The stem of the basic valve shall be guided top and bottom. The diaphragm shall not be used as a seating surface. All internal and external ferrous surfaces shall be coated with a high quality, fusion epoxy coating. The pressure pilot control shall be field adjustable from 50 psi to 200 psi. The valve shall be certified to NSF/ANSI Standard 61. The Excess Pressure Shutdown Valve shall be a WILKINS Model ZW207.