The Snow Melting Control 680 is designed to operate electric or hydronic equipment to melt snow or ice from any surface including driveways, walkways, business entrances, parking ramps, loading docks, hospital entrances, helipads and car wash bays. It communicates with Building Automation Systems using BACnet® or Modbus® for alert notification, remote monitoring and adjustment capability. Up to two snow/ice sensors can be installed, thereby increasing detection area and providing backup redundancy in the case of sensor failure. Upon detection of snow or ice, the 680 operates an electric heating cable, a single hydronic condensing or non-condensing boiler, or a steam valve to provide heat to the snow melt load. The 680 provides boiler return protection by operating a mixing valve or variable speed injection mixing. Monitoring of energy consumption is possible when it is connected to an optional flow sensor.

Features

  • Exercising
  • Automatic snow/ice detection, supports both in-slab and retrofit aerial sensors
  • Warm weather shut down, cold weather cut off
  • Energy monitoring, BACnet or Modbus communication
Spesifikasjon
  • Literature: 680_A, 680_B, 680_C, 680_D
    Control: Microprocessor control. This is not a safety (limit) control.
    Packaged weight: 6.5 lb. (2950 g)
    Dimensions: 8-1/16" H x 11-1/8" W x 2-15/16" D (204 x 282 x 74 mm)
    Display: 3-1/4", color touchscreen, 320 x 205 pixels
    Enclosure: PC+ABS plastic with steel conduit connection walls, NEMA type 1
    Approvals: CSA C US, meets class B: ICES & FCC Part 15, BTL Listed
    Ambient conditions: Indoor use only, 32 to 122°F (0 to 50°C), < 90% RH non-condensing
    Power supply: 115 V (ac) ±10%, 60 Hz, 43 VA standby, 320 VA max
    Primary, system pump relays: 230 V (ac), 10 A, 1/2 hp
    Boiler pump relay: 230 V (ac), 5 A, 1/3 hp
    Boiler stage relays: 230 V (ac), 5 A
    Boiler modulating output: 0-10 V (dc) 500 O min impedance / 4-20 mA 1 kO max impedance
    Injection mixing pump: 230 V (ac), 2.4 A
    Floating mixing output: 230 V (ac), 5 A
    Analog mixing output: 0-10 V (dc) 500 O min impedance / 4-20 mA 1 kO max impedance
    Flow sensor: 4-20 mA, 20 V (dc) power supply by control
    Pressure sensor: 0.5-4.5 V (dc) ratiometric, 10 kO min load, 5 V (dc) power supply by control
    Communications: BACnet IP, BACnet MSTP, Modbus MSTP
    Sensors: NTC thermistor, 10 kohm @ 77°F (25°C ±0.2°C) ß=3892
    –Included: Outdoor Sensor 070 and 3 of Universal Sensor 082
    –Optional: tekmar type: 072, 073, 082, 090, 094, 095
    Warranty: Limited 3 Year (See 680_D for full warranty)
Tekniske spesifikasjoner
  • Unik ref.tekmar-680
  • ProduktfamilieHVAC & Hot Water Solutions
  • ProduktgruppeControls > Snow Melting Controls
  • TypeObjekt (enkelt objekt)
  • Utgivelsesdato2020-06-14
  • Utgavenummer1
Relatert
  • Designet iCanada
  • Produsert iCanada
Klassifisering
  • BIMobject kategoriElektrisk - Adgangskontroll
  • IFC-klassifiseringElektrisk element
  • UNSPSC-navnElectrical controls and accessories
  • UNSPSC-kode391215
  • Uniclass 2015 kodePr_80_51
  • Uniclass 2015 beskrivelseMeasuring and metering products
  • CSI MasterFormat 2014 kode26 09 16
  • CSI MasterFormat 2014 tittelElectrical Controls and Relays
  • OmniClass-nummer23-27 11 15
  • OmniClass-tittelFlow Measuring Instrument And Controls
  • CSI UniFormat II kodeD3060
  • CSI UniFormat II tittelControls and Instrumentation

Tilgjengelighet etter region

Nord Amerika
Canada
USA
Common.Footer.ValueProp.Image.AltText

Design App for Revit

Last inn familier direkte i Revit-modellen din med ett klikk

Få et sted for enklere tilgang til nye objekter, lagre Revit-familiene dine og samarbeid med teamet ditt.

  • Huk avArbeid direkte med BIM-objekter ved siden av Revit
  • Huk av 2 GB skylagring – lagre Revit-innholdet ditt
  • Huk av Få LCA for innebygd karbon (A1–A3) direkte fra Revit