Releasing Module

Releasing Module

Overview

The GSA-REL is an analog addressable module that communicates directly with the fire alarm panel Signature loop controller. The GSA-REL controls sprinkler, pre-action and deluge systems, and may also be used to release extinguishing agents such as CO2 , Halon, or foam. The module is easily configured in the field and offers a wide range of options that ensure dependable service, while preventing the unnecessary release of extinguishing agent. 

In addition to being an intelligent network component, the GSA-REL interfaces with a number of conventional devices. These provide manual actuation of abort, release, and service disconnect functions. Together with the GSA-REL, they comprise a complete fire suppression package. There is no need for a separate releasing panel because the GSA-REL takes full advantage of the existing control panel communications infrastructure. This ensures low-cost installations with all the benefits of Signature Series analog initiation and control. 

  • Seven on-board circuits provide added flexibility. Each GSA-REL hosts:
  • Two supervised Class B release circuits 
  • Two supervised Class B pre-release NACs 
  • One supervised Class B manual release input circuit (latching) 
  • One supervised Class B abort circuit for normally-open abort switch (non-latching) 
  • One first alarm output relay (Form C contact) 

The GSA-REL also includes a series of built-in timers that determine the duration of abort routines and release sequences. These timers are easily configured in the field and provide a highly flexible range of options.

STANDARD FEATURES

Ideal for sprinkler, pre-action and deluge systems
Suitable for a wide range of sprinkler applications and extinguishing agents such as CO2 and Halon.

Built-in timers
Selectable durations for abort, manual, and automatic delays.

Four abort modes
Field-configurable abort routines determine how the timers operate when the abort function is initiated.

Supervised circuitry you can rely on
Two Class B release circuits and two pre-release circuits provided.

Manual operation keeps ultimate control in plain view
The GSA-REL features a manual release input circuit as well as a manual abort input circuit.

Fully automated response leaves nothing to chance
This module’s Form C relay is ideal for room preparation routines.

Automatic device mapping simplifies installation
Signature modules transmit directly to the loop controller their circuit locations with respect to other Signature devices on the wire loop.

Specifikation
  • Power riserInput voltage24 Vdc (power limited)
    Power riserSupervisory current25 mA, max.
    Power riserRiser input current4 amps maximum
    Power riserAlarm170 mA min., 4 A max.
    Release circuitsOutput rating2 A @ 24 Vdc (for each circuit)
    Release circuitsValves per circuit4 valves, max.
    Release circuitsMax. supervisory current0.4 mA (short circuit)
    Release circuitsNominal supervisory current0.18 mA
    Release circuitsSupervisory voltage26 Vdc, max. (open circuit)
    Release circuitsEnd of line device47k Ohm EOL
    Pre-release alarm circuitsOutput rating2 A @ 24 Vdc (for each circuit)
    Pre-release alarm circuitsMax. supervisory current0.4 mA (short circuit)
    Pre-release alarm circuitsNominal supervisory current0.18 mA
    Pre-release alarm circuitsSupervisory voltage26 Vdc, max. (open circuit)
    Pre-release alarm circuitsEnd of line device47k Ohm resistor
    Manual release input circuitMax. supervisory current0.4 mA (short circuit)
    Manual release input circuitNominal supervisory current0.18 mA
    Manual release input circuitSupervisory voltage26 Vdc, max. (open circuit)
    Manual release input circuitEnd of line device47k Ohm resistor
    Manual release input circuitCircuit typeClass B N.O. latching
    Manual release input circuitCircuit capacitance0.1 µF, max
    Abort circuitMax. supervisory current0.4 mA (short circuit)
    Abort circuitNominal supervisory current0.18 mA
    Abort circuitSupervisory voltage26 Vdc, max. (open circuit)
    Abort circuitEnd of line device47k Ohm resistor
    Abort circuitCircuit typeClass B N.O. non-latching
    Abort circuitCircuit capacitance0.1 µF, max
    First alarm output relayContact rating3 A @ 24 Vdc
    (0.6 power factor) Form C
    Signature Data lineOperating voltage5.2 to 19.95 Vdc
    Signature Data lineSupervisory current1000 µA
    Signature Data lineAlarm current1000 µA
    Environmental conditionsOperating temperature32° F to 120° F
    (0° C to 49° C)
    Environmental conditionsStorage temperature-4° F to 140° F
    (-20° C to 60° C)
    Environmental conditionsHumidity0 to 93% Non-condensing
    Wiring TerminalsSuitable for #18 to #12 AWG (2.5 mm² to .75 mm²)
    Type CodeFactory Set
    Addressing RequirementsUses six module addresses
    Agency ListingsUL, ULC, and FM
    Compatible SolenoidsMust be both UL/ULC-listed and FM-approved
Teknisk specifikation
  • Unik ref.releasing-module
  • ProduktfamiljFire Detection Systems
  • ProduktgruppSmoke Detection Devices
  • TypObjekt (enstaka objekt)
  • Publiceringsdatum2026-06-17
  • Edition nummer1
Relaterad
  • Designad iUSA
  • Tillverkad iUSA
Klassificering
  • BIMobjektkategoriBrandskyddsprodukter - Skyddande beläggningar
  • ETIM kodEC002455
  • ETIM namnGas detector
  • Uniclass 2015 kodPr_75_75_30
  • Uniclass 2015 beskrivningFire alarm detection devices and control equipment
  • CSI MasterFormat 2014 Kod28 33 00
  • CSI MasterFormat 2014 TitelGas Detection and Alarm
  • OmniClass nummer23-29 29 13 13
  • OmniClass TitelHeat Detectors

Region tillgänglighet

Nordamerika
Amerikanska Jungruöarna
Anguilla
Antigua och Barbuda
Aruba
Bahamas
Barbados
Belize
Bermuda
British Virgin Islands
Caymanöarna
Costa Rica
Curaçao
Dominica
Dominikanska republiken
El Salvador
Grenada
Grönland
Guadeloupe
Guatemala
Haiti
Honduras
Jamaica
Kanada
Karibiska Nederländerna
Kuba
Martinique
Mexiko
Montserrat
Nicaragua
Panama
Puerto Rico
Saint Christopher och Nevis
Saint Lucia
Saint Vincent och Grenadinerna
Saint-Barthélemy
Saint-Martin
Saint-Pierre-et-Miquelon
Sint Maarten
Trinidad och Tobago
Turks och Caicos Islands
USA
Common.Footer.ValueProp.Image.AltText

Design App för Revit

Ladda familjer direkt till din Revit-modell med ett klick

Få en plats för att enklare komma åt nya objekt, lagra dina Revit-familjer och samarbeta med ditt team.

  • BockmarkeringArbeta direkt med BIM-objekt bredvid Revit
  • Bockmarkering 2 GB molnlagring - lagra ditt Revit-innehåll
  • Bockmarkering Få inbyggd kol-LCA (A1-A3) direkt från Revit