發佈您的產品
Modular Side/Down Discharge Direct Fired Heater with Cooling Coil and V-Bank

Modular Side/Down Discharge Direct Fired Heater with Cooling Coil and V-Bank

For Direct Fired Make-Up Air Package Submittal Drawings please click here.
For Direct Fired Make-Up Air Package Performance Data please click here.

  • Air Volume: 1000 - 21000 cfm
  • Maximum SP: 4" wg. @ standard air density

    DIRECT GAS FIRED MAKE-UP AIR
    The Direct Gas Fired Make-Up Air package is designed to deliver tempered make-up air for installations requiring frequent air changes. Units are designed for natural and propane gas applications, and for indoor or outdoor installation.

    STANDARD FEATURES & BENEFITS
  • G90 galvanized construction
  • Easy access doors
  • Lifting points
  • Pre-wired, pre-piped controls
  • Horizontal or down discharge
  • Vibration isolation
  • High efficiency motors
  • Adjustable drive sheaves
  • Fully insulated casing
  • Stainless steel burner
  • 120 volt control transformer with single point electrical connection
  • Redundant gas valves
  • Intermittent spark pilot with timed safety lockout
  • Electronic flame modulation
  • High temperature limit switch
  • Airflow proving switch
  • Economizer inlet thermostat
  • Motor starter
  • Disconnect switch
  • Burner observation port

    AVAILABLE OPTIONS
  • Propane Fuel Application
  • Room Override Thermostat
  • Motorized Intake Damper
  • Remote control panel including summer/winter switch and operating lights
  • Freeze Stat with Bypass Timer
  • Hi/Low Gas Pressure Switches
  • Room Modulating Thermostat
  • High Gas Pressure Regulator
  • Convenience Outlet
  • DX Cooling Coils
  • Evaporative Cooler Intake
  • V-Bank Filter Intake
  • Sloped Filter Intake
  • Auxiliary Starters
  • Inlet Gas Pressure Gauge
  • Indoor Hanging Cradle
  • VAV Packages
  • Roof Curbs
  • Clogged Filter Switch
  • Cooling Thermostat and Interlock
  • Extra Set of V-Belts

    ADDITIONAL FEATURES
    The Direct Gas Fired Heater is ETL Listed for use in tempering make-up air. The make-up air is introduced into the heater intake directly from outside the building. Packages are certified to the ANSI Z83.4a-2001/CSA 3.7a-2001 combined safety standard and are available in sizes up to 2,500,000 BTUH and 21,000 CFM. A unique feature of our unit is the patented self-adjusting burner profile plates, which ensure proper air velocity and pressure drop across the burner for clean combustion. Spring-loaded profile plates react to the momentum of the fresh air stream, therefore, no motors or actuators are needed to drive them, nor do they need to be manually set to a specific position. With this feature, all of our units are designed for variable air volume capabilities.

    Standard features include intermittent spark ignition system with timed safety lockout and redundant gas valves. Units consist of a galvanized enclosure with an elevated gas burner which burns directly in the air stream. The burner consists of non-clogging, stainless steel combustion baffles attached to a aluminum gas supply section. The burner is capable of 100% thermal efficiency with a maximum turndown ratio of 30 to 1. The burner module has a standard horizontal inlet and discharge duct connection, and is located upstream of the blower module. The blower module has a standard horizontal inlet designed to accommodate an outside air inlet hood with standard 2" filters and screen.

    To satisfy a variety of installation requirements, packages are available in a number of configurations which include additions of a v-bank, cooling coil or an evaporative cooler intake module. All modules bolt together to form a rigid common base structure that mounts onto a single curb structure.

    Combination packages that include both exhaust and supply fans mounted on a single roof curb are also available, please contact your sales representative for more information.

    CERTIFICATIONS
    The AD Model has been certified by ITS. This certification mark indicates that the product has been tested to and has met the minimum requirements of a widely recognized (consensus) U.S. and Canadian products safety standard, that the manufacturing site has been audited, and that the applicant has agreed to a program of periodic factory follow-up inspections to verify continued performance.

    Model AD is ETL Listed under file number J20042560-001 and complies with ANSI Z83.4-Second Edition and CSA 3.7-2006 Standards.
  • 技術規格
    • 唯一參考captiveaire-028
    • 產品系列HVAC
    • 產品組合Air Handling Units
    • 類型对象(单个对象)
    • 發佈日期2011-12-01
    • 版本號1
    相關
    • 設計國家/地區美國
    • 製造國家/地區美國
    分類
    • BIMobject 類別暖通空调 - 空调
    • Uniclass 2015 代碼Ss_65_40_33_51
    • Uniclass 2015 說明Mechanical supply ventilation systems
    • CSI MasterFormat 2014 代碼23 00 00
    • CSI MasterFormat 2014 標題Heating, Ventilating, and Air Conditioning (HVAC)
    • OmniClass 編號23-33 00 00
    • OmniClass 標題HVAC Specific Products and Equipment
    • CSI UniFormat II 代碼D30
    • CSI UniFormat II 標題HVAC

    發售地區

    北美
    伯利茲
    加拿大
    千里達和多巴哥
    危地馬拉
    古巴
    哥斯達黎加
    多米尼克
    多米尼加共和國
    安圭拉
    安提瓜和巴布達
    尼加拉瓜
    巴哈馬
    巴巴多斯
    巴拿馬
    庫拉索
    格林納達
    格陵蘭島
    法屬聖馬丁
    波多黎各
    洪都拉斯
    海地
    牙買加
    特克斯和凱科斯群島
    瓜德羅普
    百慕達
    美國
    美屬維爾京群島
    聖基茨和尼維斯
    聖巴泰勒米
    聖文森與格瑞那丁
    聖皮埃爾和密克隆群島
    聖盧西亞
    英屬維爾京群島
    荷屬聖馬丁
    荷蘭加勒比區
    蒙塞拉特島
    薩爾瓦多
    開曼群島
    阿魯巴
    馬提尼克
    墨西哥