發佈您的產品
Electric cable Nexans FR-N1X6G3 Protect
Electric cable Nexans FR-N1X6G3 Protect
    Nexans

    Electric cable Nexans FR-N1X6G3 Protect

    Nexans FR-N1X6G3 Protect Cca Class- 0,6/1kV low-fire hazard, fire retardant cables.

    Nexans FR-N1X6G3 Protect cables are high quality electric cables primarily used in energy networks in hotels, schools, high constructions, hospitals, power plants, data processing centers, business centers where the risk due to fire is high (external influences BD2, BD3, BE2, BE3, CA2, CB2). They are suitable for various applications including power supply, lighting, power outlets and other electrical distribution needs.

    This range complies with strict fire safety standards, regulations being Low Fire Hazard (Low Smoke Zero Halogen materials) which makes them suitable in buildings with a high concentration of people and/or the density of population or valuable property.

    Nexans FR-N1X6G3 Protect cables can be installed in conduits, ducts, or directly in walls, floors, or ceilings (indoor applications).

    Fire performance class as per Construction Products Regulation - Cca Class.
    Complies with following:

    • Product standard: XP C32-325
    • French decree of 17 May 2024
    • NF C15-100
    規格
    • Construction:

      1. Conductor: Copper
      2. Insulation: XLPE
      3. Filler: LFH (LSZH, Halogen free)
      4. Outer sheath: LFH (LSZH, Halogen free)

      The range includes products with following constructions :

      • Circular solid conductor shape
        • Conductor flexibility : solid class 1
        • Number of cores: from 2 to 5 cores
        • Cross section: from 1.5 to 4 mm²
      • Circular stranded conductor shape
        • Conductor flexibility : stranded class 2
        • Number of cores: from 2 to 5 cores
        • Cross section: from 6 to 16 mm²


      Reminder of the definition of the external influences as listed in the standard IEC 60364-5-51

      • BD2: Emergency evacuation conditions - Low density / Difficult exit
      • BD3: Emergency evacuation conditions  - High density / Easy exit
      • BE2: Nature of materials used or stored  - Fire risks
      • BE3: Nature of materials used or stored  - Explosion risks
      • CA2: Building construction materials - Combustible 
      • CB2: Building construction materials - Propagation of fire
    技術規格
    • 唯一參考electric_cable_nexans_fr_n1x6g3_protect
    • 類型对象(单个对象)
    • 發佈日期2026-02-04
    • 版本號1
    相關
    • 主材料铜
    • 次要材料Polymer
    分類
    • BIMobject 類別电气 - Electric cables
    • IFC 分類电缆段
    • ETIM 代碼EG000001
    • ETIM 名稱Cables
    • Uniclass 2015 代碼Pr_65_70_48
    • Uniclass 2015 說明Low voltage cables
    • OmniClass 編號23-13 23 21 15
    • OmniClass 標題Cables