發佈您的產品
GORDONRAY® DF Dual-Fired Infrared Heater - (Two-Stage Operation)

GORDONRAY® DF Dual-Fired Infrared Heater - (Two-Stage Operation)

The GORDONRAY® DF features two-stage technology that can effectively adjust to sudden high heat-loss conditions, or economically maintain steady comfort levels due to the ability to fire at two distinct rates. Built to the same high standards that are expected with a ROBERTS GORDON® infrared heater, the GORDONRAY® DF is an excellent fuel efficient choice for heating in commercial/industrial applications.
The GORDONRAY® DF has a number of features that include dual burner status indicator lights, convenient external thermostat connection points that can also power a low voltage thermostat, a hinged door for easy access to electrical components during annual maintenance and fall season start-up. Maximize the radiant output by adding our new high efficiency aluminum reflectors to increase comfort levels and fuel savings.
Like our other unitary heaters, the GORDONRAY® DF has flexible layout options that include straight, u-tube, or “L” configurations along with a broad range of burner sizes and tube lengths.

規格
  • High Input (Btu/h) * (1000): 80, 100, 125, 150, 175, 200

    Low Input (Btu/h) * (1000): 55, 70, 85, 105, 120, 130

    Clearances to Combustibles (Clearances to Combustibles applies to heater hanging horizontally. Dimension listed for distance below heater.): 65in - 82in / 5.4ft - 6.8ft

    Fuel Type: Natural Gas

    Heat Exchanger Tubing: 10ft sections, 4" dia., 16 gauge, first ten feet ALUMI-THERM® steel tubing / Remaining Heat Treated Aluminized Steel Tubing

    Reflector and End Caps: .024 Aluminum (Optional- .024 Stainless Steel Type 304) 

    Control System: Fully Automatic, Three-Try, 100% Shut-off, Direct Spark Electronic Ignition Control, Dual Stage Firing Rate

    Certification: ANSI Z83.20 / CSA 2.34, 2.17, 2.20

    Warranty: Three Year Limited

    Gas-fired low-intensity infrared tube heaters are an extremely efficient and high comfort heating solution. Low-intensity tube heaters provide more design flexibility than any other type of infrared heater with the ability to direct heat only where needed in spot heating applications. Or designed to heat and maintain high comfort levels for an entire space, including buildings with high ceilings.

    Gas-fired low intensity infrared tube heaters are ideal for applications such as: loading docks (dock doors), auto/vehicle repair shops, warehouses, distribution centers, manufacturing, airplane hangars, high heat-loss areas, greenhouses (e.g. flowers, cannabis, etc...), firehouses, outdoor patios (hospitality), chicken houses, hog houses, horse barns, military, and more!

技術規格
  • 唯一參考robertsgordon-gordonraydf
  • 產品系列Commercial and Industrial Infrared Heating System
  • 產品組合GORDONRAY® DF
  • 類型对象(单个对象)
  • 發佈日期2015-02-01
  • 版本號3
相關
  • 主材料钢
  • 次要材料不锈钢
  • 設計國家/地區美國
  • 製造國家/地區美國
分類
  • BIMobject 類別暖通空调 - 加热装置
  • IFC 分類小型供暖器
  • UNSPSC 名稱Tubular heaters
  • UNSPSC 代碼40101822
  • Uniclass 2015 代碼Pr_70_60_36_72
  • Uniclass 2015 說明Radiant tube heaters
  • CSI MasterFormat 2014 代碼23 55 23
  • CSI MasterFormat 2014 標題Gas-Fired Radiant Heaters
  • OmniClass 編號23-33 15 17 13
  • OmniClass 標題Fuel Fired HVAC Radiant Heaters
  • CSI UniFormat II 代碼D3090
  • CSI UniFormat II 標題Other HVAC Systems & Equipment

發售地區

北美
加拿大
美國