Wilkins 950XLT Double Check Backflow Preventer, 3/4" to 2"
Wilkins 950XLT Double Check Backflow Preventer, 3/4" to 2"
Wilkins 950XLT Double Check Backflow Preventer, 3/4" to 2"
Wilkins 950XLT Double Check Backflow Preventer, 3/4" to 2"
Wilkins 950XLT Double Check Backflow Preventer, 3/4" to 2"
    Wilkins

    Wilkins 950XLT Double Check Backflow Preventer, 3/4" to 2"

    The Double Check Type Backflow Preventer shall be ASSE Listed 1015, rated to 180°F and supplied with full port ball valves. The main body and access covers shall be bronze (ASTM B 584), the seat ring and all internal polymers shall be Noryl™ and the seat disc elastomers shall be SILICONE. The first and second check shall be located at a 45° angle and accessible for maintenance from the top of the device, without removing the device from the line. Each check shall have separate access covers and test cocks shall be accessible from the top of the device. Test cocks shall be protected from debris by a plug. For use in non-potable applications only. The Double Check Type Backflow Preventer shall be a ZURN WILKINS Model 950XLT.

    Compliance (Unless otherwise noted, applies to 3/4" thru 2" Horizontal) 

    • ASSE® Listed 1015 (Vertical flow-up: 1 1/4" thru 2")
    • cUPC® Listed • AWWA Compliant C510 
    • CSA® Certified B64.5 (Vertical flow-up: 1 1/2" & 2") 
    • NYC MEA 426-89-M VOL 3
    • Approved by the Foundation for Cross Connection Control and Hydraulic Research at the University of Southern California (950XLTU: 3/4" & 1" Horizontal)

    Features:

    • Sizes 3/4", 1", 1 1/4", 1 1/2", 2"
    • Maximum working water pressure: 175 PSI
    • Maximum working water temperature: 180°F
    • Hydrostatic test pressure: 350 PSI
    • End connections (Threaded): ANSI B1.20.1
    規格
    • Designed for installation on water lines to protect against both backsiphonage and backpressure of polluted water into the potable water supply. A test cock plug is provided to protect against fouling caused by insects, dirt and debris. Assembly shall provide protection where a potential non-health hazard exists. For non-potable applications only.

      keywords: Double Check Assembly,Zurn Wilkins Backflow Preventers,Government Buildings,Commercial,High Rise Buildings,Hospitality,Military,Office,Retail,Healthcare,School Systems,Educational Facilities,Universities,Power Generation,Industrial,Irrigation,Architectural/Aesthetics,Correctional/Institutional,Fire Protection,Food Service,Industrial/Processing Plant,Light Commercial,Residential Multi-Family,Residential/Light Commercial,Residential Single-Family,Sports Complex/Recreational Center,Waterworks,Retrofit and Replacement,Water Conservation,Zurn Wilkins,,50XLT,0XLT,1-950XLT

    技術規格
    • 唯一參考zurn-950xlt
    • 產品系列Backflow Preventers
    • 產品組合Double Check Assembly
    • 類型对象(单个对象)
    • 發佈日期2025-09-02
    • 版本號1
    相關
    • 主材料Bronze
    • 次要材料Bronze
    • 設計國家/地區美國
    分類
    • BIMobject 類別管道 - 阀门

    發售地區

    北美
    伯利茲
    加拿大
    千里達和多巴哥
    危地馬拉
    古巴
    哥斯達黎加
    多米尼克
    多米尼加共和國
    安圭拉
    安提瓜和巴布達
    尼加拉瓜
    巴哈馬
    巴巴多斯
    巴拿馬
    庫拉索
    格林納達
    格陵蘭島
    法屬聖馬丁
    波多黎各
    洪都拉斯
    海地
    牙買加
    特克斯和凱科斯群島
    瓜德羅普
    百慕達
    美國
    美屬維爾京群島
    聖基茨和尼維斯
    聖巴泰勒米
    聖文森與格瑞那丁
    聖皮埃爾和密克隆群島
    聖盧西亞
    英屬維爾京群島
    荷屬聖馬丁
    荷蘭加勒比區
    蒙塞拉特島
    薩爾瓦多
    開曼群島
    阿魯巴
    馬提尼克
    墨西哥