The Pressure Reducing Valve shall be a diaphragm actuated, pilot controlled. The main valve body shall be Ductile Iron ASTM A 536. The stem of the basic valve shall be guided top and bottom. The diaphragm shall not be used as a seating surface. All internal and external ferrous surfaces shall be coated with a high quality, fusion epoxy coating. The pilot control shall consist of a two-way, normally open, direct acting, adjustable spring loaded, diaphragm actuated pressure reducing pilot. The pilot control shall be field adjustable from 50 psi to 165 psi. The Pressure Reducing Valve shall be a ZURN WILKINS Model ZW209FP.
Compliance:
Features:
Keywords: fire sprinkler pressure reducing valve, zurn pressure reducing valve, fire protection pressure reducing valves, fire sprinkler system pressure reducing valve, sprinkler prv, zurn pressure regulator, zurn 3/4 pressure reducing valve, zw209 zurn, pressure reducing valve sprinkler system, fire suppression valve, inline water pressure reducing valve, sprinkler pressure reducing valve, prv for sprinkler system