Pubblica i tuoi prodotti
AutoFill™ Combo Dual Check Backflow Preventer 573 - NA Market
AutoFill™ Combo Dual Check Backflow Preventer 573 - NA Market
    Caleffi

    AutoFill™ Combo Dual Check Backflow Preventer 573 - NA Market

    The automatic filling valve is a device consisting of a pressure-reducing valve with compensating seat, visual system pressure setting indicator, an inlet filter, anti-scale internal parts, a shut-off valve (round knob on bottom) and a check valve. It is installed on the water inlet piping in sealed heating systems, and its main function is to maintain the pressure of the system at a set value, automatically filling up with water as required. The valve is pre-adjustable, meaning it can be set to the desired pressure value before the system-charging phase. After installation, during the filling or topping-off phase, the water feed will stop when the set pressure is reached. This valve fills 50% faster than other valves. There are no levers to flip or valve to close. Pre-assembled with the 573 series backflow preventer, the AutoFill™ Combo features an atmospheric vent, which is designed to protect drinking water systems from return flow, caused by back-siphoning or back pressure, of contaminated fluids. The 573 series has been specifically certified to standards CSA B64.3 and ASSE 1012.

     Visit bim.caleffi.com to stay updated.

    Voce di capitolato
    • Pre-adjustable automatic filling valve with backflow preventer. Brass body. Max inlet pressure: 175 psi Max working temp: 150 degrees F Setting pressure range: 3 - 60 psi Preset outlet pressure: 15 psi.

    Specifiche tecniche
    • Rif. Unico5730XXA
    • Famiglia di prodottoHVAC
    • Gruppo di famigliaNorth America
    • TipoOggetto (oggetto singolo)
    • Data di pubblicazione2020-09-25
    • Numero di versione2
    Relativo a
    • Materiale principaleOttone
    • Materiale secondarioAcciaio inossidabile
    • Progettato inItalia
    • Prodotto inItalia
    Classificazioni
    • Categoria BIMobjectRiscaldamento, ventilazione e condizionamento - HVAC - Altro
    • Clasificazione IFCValvola
    • Codice ETIMEC011325
    • Nome ETIMCH refill installation
    • Nome UNSPSCValves
    • Codice UNSPSC401416
    • Codice Uniclass 2015Pr_65_54_95_05
    • Descrizione Uniclass 2015Backflow prevention devices
    • Codice CSI MasterFormat 201423 00 00
    • Titolo CSI MasterFormat 2014Heating, Ventilating, and Air Conditioning (HVAC)
    • Numero OmniClass23-27 31 11
    • Titolo OmniClassBackflow Preventors
    • Codice CSI UniFormat IID30
    • Titolo CSI UniFormat IIHVAC

    Disponibilità Regionale

    Nord America
    Canada
    Stati Uniti
    Common.Footer.ValueProp.Image.AltText

    App di progettazione per Revit

    Carica le famiglie direttamente nel tuo modello Revit con un solo clic

    Ottieni un posto per accedere più facilmente a nuovi oggetti, archivia le tue famiglie Revit e collabora con il tuo team.

    • Segno di spuntaLavora direttamente con gli oggetti BIM accanto a Revit
    • Segno di spunta 2 GB di spazio di archiviazione cloud: archivia i tuoi contenuti Revit
    • Segno di spunta Ottieni l'LCA (A1-A3) del carbonio incorporato direttamente da Revit