제품 게시
Z-one™ Zone Pump Controller, Multizone and Single Zone - NA Market
Z-one™ Zone Pump Controller, Multizone and Single Zone - NA Market
    Caleffi

    Z-one™ Zone Pump Controller, Multizone and Single Zone - NA Market

    The ZSR series is a zone pump and boiler operating control for single zone switching and multiple zone hydronic heating systems. The ZSR series interfaces with low voltage thermostats, or any other low voltage controllers having a switching action. The ZSR101 single zone switching relay incorporates Power In, Relay 1 and Relay 2 connection terminals to provide a convenient and cost effective way to control a circulator and a boiler operating control in a single zone hydronic heating system. The ZSR101 single zone switching relay saves hours in installation time and provides a clean and professional installation. The ZSR series multiple zone switching relay controls up to 6 zone pumps depending on model selected and a primary pump. It has LED indicators to provide functional status and easy system troubleshooting.

    PLEASE download from "DOWNLOAD" panel on this page, the Revit Content Instruction Guide, to aid in understanding what is in the Revit family and how to select various available options.

    사양
    • Z-one™ Relay, ZSR series

      Multi-zone pump switching relay. Compatible with 2, 3 and 4-wire thermostats or low voltage controllers with switching action. Power supply 120 VAC, 50/60 Hz. Zone priority selectable with 1 hour time-out feature. System pump status (on/off) during priority selectable. Transformer voltage: 24 VAC. R,W,C and T,T,COM dual labeling at thermostat terminals. Dry contacts (XX,AUX,T,T,ZONE 1 E/S) capable of switching line voltage. Automatic resettable fuse on 24 V circuit. Expandable to unlimited number of zones using 3-wire connection between controls. Large screw terminals. Front panel LED indicator light for functional status. ETL certified to CSA C22-2 No. 24, conforms to UL873. Provided with heavy duty, sealed relays, 1 primary pump output and 3 to 6 (model dependent) zone pump outputs (120 VAC/5A each), high capacity 12 VA transformer on 3 and 4 zone models, and 20 VA transformer on 6 zone models, and 3 pump ground terminals. Temperature limits for shipping, storage and operating: 110 degrees F (43 degrees C). Maximum humidity: 90 percent non-condensing. Electrical switch rating: 20A maximum combined. Electrical switch rating pump output: 120 VAC, 5A each. Dry contact rating XX,AUX,T,T,ZONE 1 E/S: 120 VAC, 2A each.

      Single-zone pump switching relay

      Materials
      Housing plastic: ABS
      Front display lights: LED
      Electrical knockouts (6) 1/2" size
      Performance
      Power supply: 120 VAC, 50/60 Hz
      Transformer voltage: 24 VAC
      Maximum transformer load: 6 VA
      Temperature limits for:
      Shipping and storage max: 110°F (43°C)
      Maximum operating: 110°F (43°C)
      Maximum humidity: 90% non-condensing
      Electrical switch rating: 10A Max combined
      Replaceable fuses: Type 2AG, 5A slow blow
      Approvals: ETL Certifi ed to CSA C22-2 No.24, Conforms to UL873

      PLEASE download from "DOWNLOAD" panel on this page, the Revit Content Instruction Guide, to aid in understanding what is in the Revit family and how to select various available options.

    기술 사양
    • 특징 참조ZSR
    • 제품군HVAC
    • 제품분류North America
    • 유형개체 (단일 개체)
    • 게시일2023-11-28
    • 에디션 넘버1
    분류
    • BIMobject 카테고리HVAC - HVAC

    지역 가용성

    북미
    미국
    캐나다
    BIMobject 제품 라이브러리

    Revit용 Design App

    한 번의 클릭으로 Revit 모델에 바로 패밀리를 로드하세요.

    새 객체에 더 쉽게 접근하고, Revit 패밀리를 저장하고, 팀과 협업할 수 있는 공간을 확보하세요.

    • 체크 표시Revit 바로 옆에서 BIM 개체로 직접 작업
    • 체크 표시 2GB 클라우드 스토리지 - Revit 콘텐츠 저장
    • 체크 표시 Revit에서 바로 내재 탄소 LCA(A1-A3) 획득