Standard Construction
Frame: 5" x 1" (127 x 25) galvanized steel hat channel with interlocking corner gusset. Equivalent to 13 ga. (2.4) channel frame. Low profile head and sill are used on sizes less than 13" (330) high.
Blades: 6" x 16 ga. (152 x 1.6) galvanized steel - triple-V.
Side-Plate: 14-5/16" x 20 ga. (364 x 1.0) galvanized steel.
Axles: 1/2" (13) diameter plated steel hex.
Linkage: Concealed in frame.
Bearings: Stainless steel oilite, sleeve-type.
Seals: Silicone blade edge seals and flexible metal jamb seals.
Actuator: 120 VAC, power-open, spring-close, external mount.
Fire Closure Device:
HS-10 (electric actuators)
PFV (pneumatic actuators)
Fire Closure Temperature: 165oF (75oC)
Minimum Size: 6" x 6" (152 x 152)
Maximum Size:
Square: 12" x 12" (305 x 305)
Rectangular: 24" (610) W or 12" (305) H with a maximum area of 144 in2. (929 cm2)
Ratings
UL 555C Fire Resistance Rating: 3 hour (horizontal, for use in 1, 2 or 3 hour rated assemblies)
UL 555 Fire Resistance Rating:
1-1/2 hour (horizontal)
1 hour (tunnel-type corridor ceiling)
UL 555S Leakage Class: 2
Maximum Temperature: 350oF (177oC)