Power
• 100 V~ 50 / 60 Hz 150 mA
• 120 V~ 50 / 60 Hz 120 mA
• 220-240 V~ 50 / 60 Hz 80 mA
• 277 V~ 50 / 60 Hz 70 mA • DALI®
• Lightning strike protection meets ANSI / IEEE standard 62.31-1980. Can withstand voltage surges of up to 6000 V~ and current surges of up to 3000 A
• DALI® Bus Output: 16 V- 128 mA guaranteed supply current, 250 mA maximum supply current per bus
Standards
• Lutron Quality Systems registered to ISO 9001:2015.
• IEC 60669-2-5
• DALI-2® certified - IEC 62386-101 and IEC62386-103 ed.2
• NOM Certified
• ICES-3(B) / NMB-3(B)
• FCC Part 15
• cULus Listed
• UL® 924
Environment
• Ambient temperature operating range: 32 ºF to 104 ºF (0 ºC to 40 ºC)
• Relative humidity: less than 90% non-condensing
• For indoor use only
Terminals
• Mains wiring: 18 AWG to 12 AWG (1.0 mm2 to 4.0 mm2)
• DALI® bus wiring: 20 AWG to 12 AWG (0.5 mm2 to 4.0 mm2)
• QS link wiring: 20 AWG to 12 AWG (0.5 mm2 to 2.5 mm2)
• CCI and CCI emergency wiring: 20 AWG to 16 AWG (0.5 mm2 to 1.5 mm2)
Mounting
• Intended to mount within an IP20 (minimum) rated consumer panel or breaker panel with integrated DIN rail and dead cover
• 9 DIN modules (161.7 mm)
• For more information on mounting and installation in panels with integrated DIN rail see the DIN Rail Best Practices Application Note (P / N 048466) at www.lutron.com
DALI® Bus
• The DALI® Power Module has an integrated bus power supply that provides a guaranteed current of 128 mA (maximum of 250 mA)
• The DALI® Power Module is a DALI® single master controller and therefore no other controller or sensor may exist on the same DALI® bus
• Some DALI® loads may be polarity sensitive; refer to individual manufacturers’ specifications for proper connection to the DALI® bus
• Short circuit protection with automatic re-start (610 ms shutdown delay with a 3 second re-start followed by 800 ms shutdown delay with 160 ms retry time)
Troubleshooting and Maintenance Features
• Maintains redundant memory of control gear programming for ease of single- and multi-control gear replacement
• After installation, “TEST” button verifies DALI® wiring on all fixtures