Publicar produtos
VK504 - ESFR Dry Pendent Sprinkler (K16.8)
Arquivado

VK504 - ESFR Dry Pendent Sprinkler (K16.8)

Successfully meets new UL 1767 test standard and compliance program for ESFR sprinklers installed in rack storage with high clearances to ceiling (20 ft or greater) Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK504 is a fast response fusible element type sprinkler designed for use in storage areas subject to freezing and supplied from a wet system only, in an adjacent heated area. With a 16.8 (242 metric*) nominal K-Factor and special deflector, this sprinkler produces large, high-momentum water droplets in a hemispheric pattern below the deflector. This permits penetration of the fire plume and direct wetting of the burning fuel surface while cooling the atmosphere early in the development of a high-challenge fire. The dry ESFR sprinkler consists of a fusible element style ESFR sprinkler permanently secured to a special supply nipple. The sprinkler assembly features a sealed brass inlet that’s grooved or threaded. Also included with the ESFR dry sprinkler are two insulating boot assemblies (optional) to help seal the clearance space around the dry sprinkler barrel. The dry sprinkler boot assembly is intended to slow the exchange of air between the inside and outside of the freezer (or any dry sprinkler installation) to help prevent humidity and temperature differential in the area around the sprinkler. Condensation can lead to ice build-up, which could inhibit sprinkler operation or cause premature operation.
Especificação
  • K-Factor: K16.8 (240)

    Manufacturer: Viking

    Page: F_062613

    Part Number: 19225,19226,19227,19229,19230,19231,19233,19234,19235,19015,19016,19017

    VK Number: VK504

    Additional Information: NOTICE: The product details indicated below are for general reference only and may vary based on the specific product approval and/or application. Always verify product details with the technical data sheet and consult with the Authority Having Jurisdiction (AHJ).

    Max Pressure: 175 psi (12 bar)

    Response Type: Fast-ESFR

    Occupancy Type: Storage

    Thread Size: 1-1/2" Grooved

    Min Spacing: Per Standards / Listings

    Max Spacing: Per Standards / Listings

Especificações técnicas
  • Ref.ª únicavk504-fast-esfr-pendent-sprinkler-k168
  • Familia de productoViking Dry Barrel Sprinklers
  • Grupo de produtosViking - Dry ESFR / Pendent
  • TipoObject (objeto único)
  • Data de publicação2021-01-25
  • Número de edição1
Relacionado
  • Concebido emUnited States
  • Fabricado emUnited States
Classificação
  • Categoria BIMobjectProdutos para fogo - Sistemas de aspersão
  • Código ETIMEC011373
  • Nome ETIMDry sprinkler
  • Nome UNSPSCFire sprinkler heads
  • Código UNSPSC46191610
  • Uniclass 2015 CódigoPr_70_55_97_84
  • Uniclass 2015 DescriçãoSprinkler heads
  • Código CSI MasterFormat 201421 13 00
  • Título CSI MasterFormat 2014Fire-Suppression Sprinkler Systems
  • Número OmniClass23-29 33 11 11 13
  • Título OmniclassDry Pendant Sprinkler Heads
  • Código CSI UniFormat IID4010
  • Título CSI UniFormat IISprinklers
Common.Footer.ValueProp.Image.AltText

Aplicação de design para Revit

Carregue famílias diretamente no seu modelo Revit com um clique

Tenha um local para acessar novos objetos com mais facilidade, armazenar suas famílias Revit e colaborar com sua equipe.

  • Marca de seleçãoTrabalhe diretamente com objetos BIM ao lado do Revit
  • Marca de seleção 2GB de armazenamento na nuvem - armazene o seu conteúdo Revit
  • Marca de seleção Obtenha LCA (A1-A3) de carbono incorporado diretamente do Revit